GRP Water Tank is designed to satisfy the following basic requirements by using GRP Panel ; Long life, Hygienic,
Non-Leakage, Stable Construction and Easy Assembly etc.
We also satisfy all safety requirements such as strength, durability and stability.
Using standardized panels with bolt assembly way, you are able to adjust the water tank capacity
according to the size and structure of the building.
Design Standard of GRP Water Tank
Design Range
Range
Available Design Conditions
Height
1.0 ~ 5.0 M
Capacity
1 ~ 20,000 Ton (CBM)
Shape
Square, ㄱshape, ㄴshape, ㅁshape etc.
Section
Design Standard
Hydrostatic Pressure
Water pressure enforcement 4 times standard Transformation rate in filled up with water : Less than 1% form Water tank Height
Wind Force
Less than 60m/sec
Earthquake Force
Horizontal lntensity kh = 1/3G
Snow load
200 ㎏/㎡ , Snow fall less than 1M
lllumination Rate
Less than 1%
Out-fit Force
No leakage under condition of vertical 100㎏ after install of 100A Fitting
Water Temperature
Usable temperature : Under 30℃ Limited temperature : Under 60℃